Batteries - recommended, not included

Batteries are not included they are sold separately

Batteries are sold separately.

Battery combinations withBattery box 24V FLX S, (14 Ah batteries)

Battery capacity (Ah)

Battery type

Number of batteries

Batteries in unit

14 Ah

14 Ah

2 pcs.

2 in Battery Backup

42 Ah

14 Ah

6 pcs

2 in Battery Backup

4 in Battery Box

70 Ah

14 Ah

10 pieces.

2 in Battery Backup

4 in Battery Box

4 in battery box 2

Battery combinations Battery box 24V FLX M and battery backup (20 Ah batteries)

Battery capacity (Ah)

Battery type

Number of batteries

Batteries in unit

20 Ah

20 Ah

2 pcs

2 in Battery Backup

45 Ah

45 Ah

2 pcs

0 in Battery Backup

2 in Battery Box 1

65 Ah

20 Ah +

45 Ah

4 st

2 in Battery Backup

2 in Battery Box 1

90 Ah

45 Ah

4 st

0 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

110 Ah

20 Ah +

45 Ah

6 st

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

135 Ah

45 Ah

6 st

0 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

155 Ah

20 Ah +

45 Ah

8 st

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

180 Ah

45 Ah

8 st

0 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

2 and Batteribox 4

200 Ah

20 Ah +

45 Ah

10 pieces

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

2 and Batteribox 4

Battery combinations Battery box 24V FLX M and battery backup (45 Ah batteries)

Battery capacity (Ah)

Battery type

Number of batteries

Batteries in unit

45 Ah

45 Ah

2 pcs.

2 in Battery Backup

90 Ah

45 Ah

4 pcs

2 in Battery Backup

2 in Battery Box 1

155 Ah

45 Ah

6 pcs

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

180 Ah

45 Ah

8 pcs

0 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

225 Ah

45 Ah

10 pieces.

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

2 and Batteribox 4

Battery combinations

Battery combinations possible with

EN54 5A FLX M

EN54 10A FLX M

EN54 15A FLX M

EN54 25A FLX M

Battery box 24V FLX M

Table 1. Battery combinations for FLX M and battery box 24V FLX M

Battery capacity

Number of batteries

Unit + battery box

20 Ah

2 pcs 20 Ah

24V 5A-10A FLX M

45 Ah

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

65 Ah

2 pcs 20 Ah

2 pcs 45 Ah

24V 5A-10A FLX M

Battery box 24V FLX M

90 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

110 Ah

2 pcs 20 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

Battery box 24V FLX M

135 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

Battery box 24V FLX M

155 Ah

2 pcs 20 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

Battery box 24V FLX M

Battery box 24V FLX M

180 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

Battery box 24V FLX M

Battery box 24V FLX M

200 Ah

2 pcs 20 Ah

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

2 pcs 45 Ah*

24V 5A-10A FLX M

Battery box 24V FLX M

Battery box 24V FLX M

Battery box 24V FLX M

Battery box 24V FLX M



It is the installer's responsibility to check that the battery combinations are possible.

* Batteries in battery box.

Certified with battery type

The device is certified with a UPLUS battery that must be used to maintain the certificate.

Recommended battery type

12 V maintenance-free batteries, type AGM.

2.3 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

2.3 Ah

Table 2. 6+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V02-01

5230578

UPLUS 12V 2.3Ah 6+ Design Life battery

Flat pin 4.8 mm

60x178x35 mm

1.0 kg

UPLUS



4.5 Ah 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

4.5 Ah

Table 3. 6+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V04-01

5230577

UPLUS 12V 4.5Ah 6+ Design Life battery

Flat pin 4.8 mm

107x90x70 mm

1.5 kg

UPLUS



7.2 Ah, 12 V AGM battery

Fits in

Number of batteries

Batterybox 24V FLX S

4

PoE injector 1p S

1

PoE switch 4p FLX S

4

PoE switch 4p M

4

EN54 24V 1.5A MX S

2

SDS LAMP2

2

PSF 600W

2

SINUS UPS 200W S

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

7.2 Ah

Table 4. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V07-01

5230536

UPLUS 12V 7.2Ah 10+ Design Life battery

Flat pin 6.3 mm

151 x 65 x 100 mm.

2.4 kg

UPLUS



14 Ah, 12 V AGM battery

Fits in

Number of batteries

Batterybox 24V FLX S

4

PoE Switch 4p FLX M

4

BT-5 FLX Small COM Gen 2

2

BT-10 FLX Small COM Gen 2

2

NOVA 24V 5A FLX S

2

NOVA 24V 10A FLX S

2

SDS LAMP2

2

SINUS UPS 300W M

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

14 Ah

Table 5. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V14-01

5230537

UPLUS 12V 14Ah 10+ Design Life battery

Flat pin 6.3 mm

151x98x101 mm

4.2 kg

UPLUS



20 Ah, 12 V AGM battery

Fits in

Number of batteries

EN54 24V 5.5A MX M

2

BT-5 FLX Medium COM Gen 2

2

NOVA 12V 10A FLX M

2

NOVA 24V 5A FLX M

2

NOVA 24V 10A FLX M

2

NOVA 24V 15A FLX M

2

NOVA 24V 25A FLX M

2

NEO 24V 5A FLX M

2

NEO 24V 10A FLX M

2

NEO 24V 15A FLX M

2

NEO 24V 25A FLX M

2

EN54 24V 5A FLX M

2

EN54 24V 10A FLX M

2

EN54 24V 15A FLX M

2

EN54 24V 25A FLX M

2

PoE M-Switch 4p FLX M

2

PoE M-Switch 8p FLX M

2

PoE M-Switch 16p FLX M

2

SINUS 1100W FLX M

2

SINUS 600W FLX M

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

20 Ah

Table 6. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V20-01

5230538

UPLUS 12V 20Ah 10+ Design Life battery

M5 Bult

182x77x168 mm

6.0 kg

UPLUS



28 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

28 Ah

Table 7. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V28-01

5230545

UPLUS 12V 28Ah 10+ Design Life battery

M5 Bult

165x125x175 mm

9.5 kg

UPLUS



45 Ah, 12 V AGM battery

Fits in

Number of batteries

Batterybox 24V FLX M

2

EN54 24V 5.5A MX S

2

NE0 24V 5A FLX L

2

NE0 24V 10A FLX L

2

NE0 24V 15A FLX L

2

NE0 24V2 5A FLX L

2

NOVA 24V 5A FLX L

2

NOVA 12V 10A FLX L

2

NOVA 24V 10A FLX L

2

NOVA 24V 15A FLX L

2

NOVA 24V2 5A FLX L

2

BT-5 FLX Large COM Gen 2

2

BT-10 FLX Large COM Gen 2

2

BT-15 FLX Large COM Gen 2

2

BT-25 FLX Large COM Gen 2

2

SINUS 1100W FLX L

2

TEL-1200W-STS-SIN2

2

SINUS 1500W FLX L

2

SINUS 600W FLX L

2

TEL-350W-STS-SIN2

2

TEL-600W-STS-SIN2

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

45 Ah

Table 8. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V45-01

5230546

UPLUS 12V 45Ah 10+ Design Life battery

M5 Bult

197x165x170 mm

14.5 kg

UPLUS



75 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

75 Ah

Table 9. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V75-01 ***

5230547

UPLUS 12V 75Ah 10+ Design Life battery

M6 Bult

295x168x214 mm

21 kg

UPLUS



100 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

100 Ah

Table 10. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V100-01 ***

5230549

UPLUS 12V 100Ah 10+ Design Life battery

M8 Bult

330x173x212 mm

30 kg

UPLUS



150 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

150 Ah

Table 11. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V150-01 ***

5230561

UPLUS 12V 150Ah 10+ Design Life battery

M8 Bult

485x170x240 mm

43.5 kg

UPLUS



55 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

55 Ah

Table 12. 12+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V55-FT ***

5230562

UPLUS 12V 55Ah 12+ Design Life battery

M6 Bult

277x106x222 mm

18 kg

UPLUS



60 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

60 Ah

Table 13. 15+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V62-FT ***

-

UPLUS 12V 60Ah 15+ Design Life battery

M6 Bult

267x97x299 mm

20 kg

UPLUS



62 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

62 Ah

Table 14. 15+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V62XL-00 ***

5230566

Powersafe 12V 62Ah 15+ Design Life battery

M6 Bult

267x97x299 mm

20 kg

Enersys



90 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

90 Ah

Table 15. 15+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V92-FT ***

-

UPLUS 12V 90Ah 15+ Design Life battery

M6 Bult

287x108x406 mm

29 kg

UPLUS



100 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

100 Ah

Table 16. 12+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V100-FT ***

5230563

UPLUS 12V 100Ah 12+ Design Life battery

M6 Bult

285x110x394 mm

35.6 kg

UPLUS



MT114-12V125-FT *

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

125 Ah

Table 17. 12+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V125-FT ***

5230564

UPLUS 12V 125Ah 12+ Design Life battery

M6 Bult

287x110x551 mm

40.5 kg

UPLUS



150 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

150 Ah

Table 18. 12+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V150-FT ***

5230565

UPLUS 12V 150Ah 12+ Design Life battery

M6 Bult

287x110x551 mm

46.0 kg

UPLUS



7.5 Ah, 12 V Lithium battery

The batteries are of the type Lithium-iron phosphate cells (LiFePo4) and have protection against overcharging and discharging. Lithium batteries (Sellpower) have extremely low self-discharge, can be used in temperatures from -20 ° C to + 60 ° C for about 2,000 charge cycles.

Battery type

V

Ah

Lithium-iron phosphate cells (LiFePo4)

12 V

7.5 Ah

Table 19. 15+ Design life Lithium * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

SPLi12-7.5 ***

-

Sellpower 12V 7.5Ah 15+ Lithium battery

Flat pin 6.3 mm

151x65x94 mm

1.1 kg

Sellpower



12 Ah, 12 V Lithium battery

The batteries are of the type Lithium-iron phosphate cells (LiFePo4) and have protection against overcharging and discharging. Lithium batteries (Sellpower) have extremely low self-discharge, can be used in temperatures from -20 ° C to + 60 ° C for about 2,000 charge cycles

Battery type

V

Ah

Lithium-iron phosphate cells (LiFePo4)

12 V

12 Ah

Table 20. 15+ Design life Lithium * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

SPLi12-12 ***

-

Sellpower 12V 12Ah 15+ Lithium battery

Flat pin 6.3 mm

151x98x95 mm

1.7 kg

Sellpower



20 Ah, 12 V Lithium battery

The batteries are of the type Lithium-iron phosphate cells (LiFePo4) and have protection against overcharging and discharging. Lithium batteries (Sellpower) have extremely low self-discharge, can be used in temperatures from -20 ° C to + 60 ° C for about 2,000 charge cycles

Battery type

V

Ah

Lithium-iron phosphate cells (LiFePo4)

12 V

20 Ah

Table 21. 15+ Design life Lithium * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

SPLi12-20 ***

-

Sellpower 12V 20Ah 15+ Lithium battery

M5 Bult

181x77x167 mm

2.7 kg

Sellpower



26 Ah, 12 V Lithium battery

The batteries are of the type Lithium-iron phosphate cells (LiFePo4) and have protection against overcharging and discharging. Lithium batteries (Sellpower) have extremely low self-discharge, can be used in temperatures from -20 ° C to + 60 ° C for about 2,000 charge cycles

Battery type

V

Ah

Lithium-iron phosphate cells (LiFePo4)

12 V

26 Ah

Table 22. 15+ Design life Lithium * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

SPLi12-26 ***

-

Sellpower 12V 26Ah 15+ Lithium battery

M8 Bult

175x166x125 mm

4.2 kg

Sellpower



45 Ah, 12 V Lithium battery

The batteries are of the type Lithium-iron phosphate cells (LiFePo4) and have protection against overcharging and discharging. Lithium batteries (Sellpower) have extremely low self-discharge, can be used in temperatures from -20 ° C to + 60 ° C for about 2,000 charge cycles

Battery type

V

Ah

Lithium-iron phosphate cells (LiFePo4)

12 V

45 Ah

Table 23. 15+ Design life Lithium * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

SPLi12-45 ***

-

Sellpower 12V 45Ah 15+ Lithium battery

M8 Bult

197x165x170 mm

7.5 kg

Sellpower



Reserve operating times for different alarm classes - overview

The table shows the requirements for backup operating time and recharging of batteries for different alarm classes.

Important

This is a guide and all times are approximate and may differ from actual times. Load, temperature and other factors come into play, which is why exact time can not be provided.

Applies to new batteries.

Amperage and batteries vary with configuration, check if the configuration can handle batteries and amperage.

Table 24. Backup operating times 12 V units - without battery box

Medium current

14 Ah

2 st 7.2 Ah

batteries)

28 Ah

(2 st 14 Ah

batteries)

40 Ah

(2 pcs 20 Ah

batteries)

Loading

Backup operating time  (approx.), Minutes

1 A

485

970

1300

2 A

380

560

810

4 A

165

330

490

6 A

120

245

360

8 A

100

210

310

10 A

80

160

240



Table 25. Backup operating times 24 V units - without battery box

Medium current

7.2 Ah

14 Ah

28 Ah

45 Ah

Loading

Backup operating time  (approx.), Minutes

0.5 A

450

820

1650

2350

1 A

260

485

970

1460

2 A

150

280

560

920

4 A

90

165

335

550

6 A

67

125

245

405

8 A

57

105

210

350

10 A

44

80

160

270

12 A

38

70

140

235

14 A

33

60

120

200

16 A

28

50

100

170

18 A

25

45

89

150

20 A

23

42

84

142



Table 26. Backup operating times  24 V units - with battery box, 28 Ah - 70 Ah

Medium current

28 Ah

42 Ah

65 Ah

70 Ah

-

4 batteries

(14 Ah)

6 batteries

(14 Ah)

4 batteries

(20Ah + 45 Ah)

10 batteries

(7 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

1650

2090

5574

3440

1 A

970

865

3252

2118

2 A

560

815

1770

1329

4 A

335

490

930

864

6 A

245

360

600

605

8 A

210

310

426

544

10 A

160

240

342

414

12 A

140

210

270

363

14 A

120

180

234

311

16 A

100

150

204

286

18 A

90

130

150

254

20 A

84

126

138

241



Table 27. Backup operating times 24 V units - with battery box, 90 Ah - 155 Ah

Medium current

90 Ah

110 Ah

135 Ah

155 Ah

-

4 batteries

(45 Ah)

6 batteries

(20 Ah + 45 Ah)

6 batteries

(45 Ah)

8 batteries

(20 Ah + 45 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

4705

5796

7056

8215

1 A

2928

3582

4392

5070

2 A

1836

2247

2754

3230

4 A

1183

1438

1762

2018

6 A

788

959

1175

1345

8 A

748

861

1048

1150

10 A

570

689

839

920

12 A

499

603

699

765

14 A

427

516

629

655

16 A

404

499

592

590

18 A

359

444

526

520

20 A

340

420

498

495



Table 28. Backup operating times 24 V units - with battery box, 180 Ah - 225 Ah

Medium current

180 Ah

200 Ah

225 Ah

-

8 batteries

(45 Ah)

10 batteries

(20 Ah + 45 Ah)

10 batteries

(45 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

9408

12972

11760

1 A

5856

7872

7320

2 A

3672

4548

4590

4 A

2365

2670

2945

6 A

1577

1780

1960

8 A

1500

1558

1800

10 A

1140

1246

1410

12 A

950

1038

1200

14 A

855

890

1055

16 A

810

902

995

18 A

715

802

885

20 A

680

722

840



-

90 Ah, 4 batteries (45 Ah)

Loading

Estimated battery life

300 W

360 minutes

Subject to typos.

100 Ah, 12 V AGM battery

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

100 Ah

Table 29. 12+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT114-12V100-FT ***

-

UPLUS 12V 100Ah 12+ Design Life battery

M6 Bult

285x110x394 mm

35.6 kg

UPLUS



The product lacks batteries

This product does not have a battery / batteries.

Maintenance schedule batteries

The maintenance schedule applies to batteries made by UPLUS and with the following serial names: US, USL, USF, and for batteries made by XLENT POWER with serial names XLT and XLL. For maintenance instructions see separate document "care instructions valve-regulated lead-acid battery”.Maintenance Instructions batteries

Table 30. Battery replacement

Series designation

Battery type

Replace battery after

XLT

3-5 years

2-3 years

US

6-9 years

3-5 years

USL

10-12 years

5-7 years

USF

12 years

8-10 years

* battery life depends mainly on ambient temperature and charging current. An AGM battery should never be charged with more than 30% of its rated capacity. The battery will be fully charges, but the charning current must not excced 30% of its rated capacity.



Table 31. Charging voltages

Charging voltage from power supply

12 V units

24 V units

48 V units

Minimum charging voltage

13.6 V

27.2 V

54.4 V

Maximum charging voltage

13.7 V

27.4 V

54.8 V

Tolerance

+/- 0.5%

+/- 0.5%

+/- 0.5%



Table 32. terminal voltage

terminal voltage

After 15 minutes of rest / charging.

Minimum terminal voltage

12.9 V

Maximum allowable difference between battery pairs

0.5 V

New battery with terminal voltage below 12.0 V is defective and should be reported to the supplier.



Table 33. Ambient temperature for batteries

Temperature in battery backup

Temperature

Lowest

15 ° C

Recommended

20 ° C - 25 ° C

Highest

32 ° C

Warranty is valid only if the temperature is within these levels.



Installation control batteries

  1. Check that the battery is completely clean and that the terminals are free from corrosion.

  2. Check and note the temperature in the battery compartment.

  3. Check the terminal voltage of each battery before installation. If the difference between the batteries exceeds 0.5 V, the battery loop should be equalized in connection with installation. If any battery has a terminal voltage of less than 12V, this battery must be replaced with a new battery and reported to the supplier.

  4. Connect the battery and check the charging voltage. The charging voltage should be between 2.25 V - 2.27 V per cell = between 13.5 V - 13.62 V for a 12 V system and between 27.0 V - 27.24 V for a 24 V system.

Year-round inspection

  1. Check that the battery is completely clean and that the terminals are free from corrosion. If there is corrosion on the terminals: Check that the battery does not leak acid. Then clean the terminals and reconnect the battery. Then lubricate with battery terminal grease over the connected terminal.

  2. Check and note the temperature in the battery compartment.

  3. Check and note the average current.

  4. Check that all connections are securely fastened and that there is no gap in the connection.

  5. Check that the fan (if units have a fan) is working properly. Clean the fan if necessary.

  6. Check the charging voltage by measuring with a multimeter between the connection points + & amp; -. The charging voltage should be between 2.25-2.27 volts per cell = between 13.5-13.62V for a 12V system and between 27-27.24V for a 24V system.

  7. Turn off the rectifier and let the batteries rest for 10 - 15 minutes. Then measure the terminal voltage of each battery. After resting, the terminal voltage must be between 12.9 V - 13.5 V.

Information - Batteries purchased by Milleteknik

We count batteries as sellable and in good condition 14 months from the date of manufacture. Batteries are marked by the battery manufacturer and we aim for the time from the manufacturing date of the battery to the time a battery leaves us to be as short as possible. Then our customers get the best reliability. Milleteknik has carefully selected a battery supplier as there are large differences in quality and thus the lifespan of batteries. We sell three types of lead-acid batteries: 6+ Design life* - batteries with a service life in standby power of 2-3 years. 10+ Design life* - batteries with a service life in standby power of 5-6 years. 12-15+ Design life* - batteries with a service life in standby power of 6-8 years. *Design life refers to durability of a battery that has not been used. Batteries generate energy through a chemical process that never completely stops, even if the battery is not in use. When a battery is used, the chemical process increases and the life of the battery decreases. Design Life thus does not refer to a battery's lifespan. A battery's lifespan depends on a variety of factors, with use and heat being the main causes of shorter lifespan.

About translation of this document

User manual and other documents are in the original language in Swedish. Other languages may be machine translated and/or not reviewed, errors may occur.