Do I need to set the battery capacity if I install a battery box?
Battery backup with battery box | Motherboard | Can battery capacity be set? | Does battery capacity need to be set? | Is the remaining battery life calculated correctly? | |
---|---|---|---|---|---|
ECO M with 1 battery box M | CEO | No | No | - | It is not possible to read out the remaining battery time from ECO. |
ECO FLX S with 1 battery box | CEO | No | No | - | It is not possible to read out the remaining battery time from ECO. |
NEO FLX S with 1 battery box | NEO3 | No | No | - | It is not possible to read out the remaining battery time from the NEO. |
NEO FLX M with 1-4 battery boxes | NEO3 | No | No | - | It is not possible to read out the remaining battery time from the NEO. |
NEO FLX M with 1-4 battery boxes | NEO3 | No | No | - | It is not possible to read out the remaining battery time from the NEO. |
EN54 FLX M with 1-4 battery boxes | PRO2 v3 | No | No | - | It is not possible to read out the remaining battery time with battery boxes. |
EN54 1U/2U with battery shelves | RACK, 1 HE | Yes | Yes | - | Battery capacity is set on the battery backup. |
EN54 MX | MX | No | No | - | MX cannot have battery boxes connected to it, it is also not possible to read out the remaining battery time. |
PoE, all of them. | CEO | No | No | - | PoE cannot have batti boxes connected to it. It is not possible to read the remaining battery time from PoE. |
NOVA FLX S with 1 battery box | PRO1* | Yes | Yes | 14 Ah | Battery capacity is set via dip switches on the motherboard. |
NOVA FLX M with 1-4 battery box | PRO1* | Yes | Yes | 20 Ah | Battery capacity is set via dip switches on the motherboard. |
NOVA FLX L with 1-4 battery box | PRO1* | Yes | Yes | 45 Ah | Battery capacity is set via dip switches on the motherboard. |
NOVA FLX S with 1 battery box | PRO3 | No | No | 14 Ah | Battery capacity does not need to be set. The battery capacity can be set via compatible UC**. |
NOVA 24V 5A-10A FLX M with 1-4 battery boxes | PRO3 | No | No | 20 Ah | Battery capacity does not need to be set. Remaining battery time can only be read from a fixed value** and cannot be changed. |
NOVA 24V 15A-25A FLX M with 1-4 battery boxes | PRO2 v3 | No | No | 20 Ah | Battery capacity does not need to be set. Remaining battery time can only be read from a fixed value** and cannot be changed. |
NOVA 24V 5A-10A FLX L with 1-4 battery boxes | PRO3 | No | No | 45 Ah | Battery capacity does not need to be set. Remaining battery time can only be read from a fixed value** and cannot be changed. |
NOVA 24V 25A-15A FLX L with 1-4 battery boxes | PRO2v4 | No | No | 45 Ah | Battery capacity does not need to be set. Remaining battery time can only be read from a fixed value** and cannot be changed. |
*The PRO1 card is being phased out and is no longer sold.
**Remaining battery time is read from a fixed value, compatible UC can also change this value. Sentrion can only read value from battery backup and it is not possible to set battery capacity from Sentrion. Battery backup in Sentrion will always calculate the value of remaining battery time from the factory-set value in battery backup.
Support
Do you need help with installation or connection?
You will find answers to many questions at: www.milleteknik.se/support
Phone: +46 31-340 02 30
Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.
Spare parts
Contacted support for questions about spare parts.
Support after the warranty period
Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are added after the warranty period has expired.
Questions about product performance?
Contact sales: 46 31-340 02 30, e-mail: sales@milleteknik.se
About translation of this document
User manual and other documents are in the original language in Swedish. Other languages may be machine translated and/or not reviewed, errors may occur.