About Sinus UPS from Milleteknik

The SIN inverter is an Off-line UPS that steps in and replaces the supply from the mains in the event of a mains failure, until the mains returns (or the batteries are completely discharged). SIN inverters are designed with the latest switching technology and microprocessor monitoring, for: Highest efficiency and operational reliability, providing long life for both electronics and batteries. Well protected with , protection against overtemperature, overload, short circuit. Complete self-test including advanced battery test. The units are installation and service friendly: Compact volume. Modular structure.

The UPS is charged with a built-in power supply and is powered further by batteries in the event of a power failure.

Safety - read this first

  • The unit must be installed by a qualified person.

  • It is the installer's responsibility that the system is suitable for intended use.

  • Documents accompanying the system must be kept in its immediate vicinity.

  • The system should not be connected to the mains during installation.

  • All information is subject to change.

Danger

Dangerously high voltage.

Wait one (1) minute after power has been disconnected from the unit.

About translation of this document

User manual and other documents are in the original language in Swedish. Other languages are machine translated and not reviewed, errors may occur.

Component overview

SIN_300W_M_Komponentoeversikt.png
Table 1. Component overview

Letter

Explanation

A

Cabinet in powder-coated sheet metal.

B

Batteries.

C

Power supply unit

D

Automatic fuse battery.

E

Motherboard.

F

Cable entries.



Enclosures

Wall mounting

Use four screws suitable for the wall to set up the cabinet.

The distance between the screw head and the wall should be 1.5–2 mm.

Preferably leave a 100 mm air gap around the unit.

M_baksida_skiss.png

Mounting

Use the appropriate screw for mounting on the wall, Screw for mounting on the wall is not included.

Connection 230 V

In: Battery connection

230_V_in_SIN_300W_M_Komponentoeversikt.png
Table 2. Overview of incoming mains and battery connection

I

Battery wiring

II

Battery wiring for automatic fuse



Connect Phase/Neutral/Earth (PE) incoming on motherboard

Table 3. Battery number

B1, B2

Explanation

B1+

+ from circuit board to battery

B1-

- from fuse to battery.

B2+

+ from fuse to battery.

B2-

- from circuit board to battery.



Load disconnector incoming mains (in: 230 V)

For maximum safety, always disconnect from the mains before installation and service. Connect a load disconnector (circuit breaker) to the incoming cable from the mains. Place it easily accessible and label it clearly. With a load disconnector installed, incoming voltage can be easily interrupted during service and function tests.

Out: 230 V

Output phase/load to PICTO marked 9 on circuit board overview and 4 on circuit board. Output phase/load to (EMERGENCY LIGHT) marked 8 on circuit board overview and 5 on circuit board, (only energized in case of mains failure). Output zero, to ZERO, labeled 7 on circuit board overview and 6 on circuit board. Protective earth, PE, marked 6 on circuit board overview and 7 on circuit board.

Description motherboard: MiniSinus

Figure 1. Minisinus consists of two cards.
Minisinus consists of two cards.


Minisinus_I.png
Table 4. Circuit board overview, explanation

No

On circuit board

Explanation

1

F1

Fuse from power supply, 24 VDC for battery charging.

2

N Test load

Disconnects from the factory.

3

L Test load

4

N UPS

5

L UPS

6

PE

Protective ground, Output

7

Zero / Neutral

Zero, Output

8

(LED 0/230 V)

(Outgoing load, 230 V. Connection to emergency light/indicator light. Only voltage in case of mains failure)

9

PICTO 230 V / 230 V

Output load, 230 V. Connection to pictogram. Always phase voltage

10

LINE

Mains voltage connection: 230 V In (PHAS in)

11

NEUTRAL

Connection mains voltage: 230 V Zero

12

PE

Connection mains voltage: 230 V Protective earth, PE

13

(PHASE 230 V)

Disconnects from the factory.

14

(ZERO 230 V)

15

J5, J11, J31, J33



Minisinus_II.png

No

On circuit board

Explanation

16

10

9

8

Self-diagnosis, NC

Self-diagnosis, COM

Self-diagnosis, NO

17

7

6

5

Mains failure alarm, NC

Power failure alarm, COM

Mains failure alarm, NO

18

Summer

Connection to buzzer

19

4

+5V

20

3

B+ (RS-485, upcoming feature)

21

2

A- (RS-485, upcoming function)

22

1

GND

23

S1

Dip switch - must not be changed

24

J16

Not used, factory connected

25

J8

26

J4

27

J24

28

P3

Not available

29

P4

Alarm connection

Self-test and alarm for mains failure

Total alarm for self-test: Connect total alarm for self-test (Self Diagnosis).

P1:1-3, incorrect charging voltage (over/undervoltage), aged battery - when the battery should be replaced, or non-functioning inverter to circuit board terminal P1:1-3. Alarm - contact NO and CO. Mains failure: Connect the mains failure alarm P1:1-3, "MAINS ALARM", an alarm is given immediately in the event of a mains failure.

Commissioning - how to start the unit

After connection, start-up must take place in the following steps:

Table 5. Commissioning - the order

Step

Explanation

1

Switch the fuse to 0/OFF and open the cabinet.

2

Connect input and output cable and alarm.

3

Close the cabinet and switch the fuse to ON/1.

4

Connect to the mains.

5

The system starts up automatically. LED indication on the cabinet door flashes until it lights up solid green. The UPS is commissioned and activated. The load is fed directly from the mains in normal mode and from the batteries via the inverter in battery operation. Switching time is typically 20ms.

6

Temporarily disconnect mains voltage to test that the UPS is working (connected load continues to be powered in battery mode).

7

Reconnect to mains voltage.



Care instructions UPS

The unit is maintenance-free when installed in a room temperature indoor environment +15°C—+25°C. However, the batteries should be changed after 10-12 years to maintain high guaranteed safety. In the extended temperature range +5°C—+15°C/+25°C—+30°C, the batteries will age twice as fast. Further colder or warmer ambient temperature means that reliability is at risk.

Battery replacement UPS

Warning

Fuse on the lid does not interrupt current (230 V) but only interrupts voltage to batteries (24 V).

Step

Explanation

1

Set fuse "0" and open the cabinet. This disconnects batteries. The device is still energized.

2

For safety's sake, also disconnect the mains voltage.

3

Disconnect the battery cables and replace the battery. Be careful not to short-circuit the battery! Note and be careful with orientation regarding battery poles +/- and the location of battery cables!

5

Connect the battery cables. Be careful not to short-circuit batteries!

6

Close the electrical cabinet and set the fuse to "1".

8

Reconnect the mains if it has been disconnected.

9

The SelfTestSystem starts up automatically. LED indication on the cabinet door flashes until it lights up steady GREEN. The UPS is commissioned and activated. The load is fed directly from the mains in normal mode and from the batteries via the inverter in battery operation. Switching time is 20 ms.

10

Temporarily disconnect mains voltage to test that the UPS is working (connected load continues to be powered in battery mode).

11

Reconnect to mains voltage.

Dimensioning UPS

Dimension the connected load so that it is, in total, as large as the inverter's maximum rated power (W), preferably less to partly obtain safety margins, and partly to compensate for losses in connections/cabling and the load which means greater actual power consumption from the inverter than the specified rated power of the load. Take temporary starting power into account, so that it does not exceed the specified maximum - short-term - starting power (VA) of the inverter. Back-up load operation should take place within one hour of the grid failure occurring, as the inverter consumes power at idle, which gradually drains the batteries.

Alarm / status on indicator diode

Alarm is shown on the indicator diode on the cabinet door.

Mains operation/mains interruption alarm: During normal mains operation, the LED on the front panel is constantly lit. In the event of a mains failure, the inverter starts in battery operation, whereby the LED flashes "1 blink" ORANGE so that when the time for any set time delay of the mains alarm occurs, the LED blinks "2 blinks" ORANGE. In the event of a "mains failure" alarm, the alarm contact switches to contact between NO-CO.

Front panel and status indicators

222-069.png

SIN UPS 300W M

Indicator diode

Text

Explanation

Green, solid glow

Okay

The device is working normally

Green blinks

Power outage

230 V mains failure

Yellow, solid glow

Low battery voltage in UPS operation

Yellow flashes

Aged battery

Battery needs to be replaced

Red, solid light

Over-undervoltage

Voltage fault

Red flashes

UPS ERROR

Over temperature, over current or feedback error.

Black / off

Deep discharge protection

Deep discharge protection has kicked in

FAQ UPS

Control measures in case of alarm UPS - Battery charge, over or under voltage

Over or under voltage is indicated if the device, when the batteries are charged, does not provide the correct charging voltage. Alarms are indicated by flashing on the front panel at the same time as a total alarm is set.

Action in case of alarm: Check charging voltage. Measure voltage to 27.3 V. At two-pole power supply terminal, (red plus, black minus cable).

Control measures in the event of an alarm UPS - Alarm for aged battery

The batteries' capacity and aging are tested weekly. If the test shows that the battery capacity has dropped below 60% - 80% of the battery's original capacity, an alarm is given for an aged battery

Action in case of alarm: Replace batteries.

Control measures in case of UPS alarm - UPS fault / inverter fault

In the event of an inverter fault, the LED on the front panel flashes at the same time as a total alarm is set.

Action in case of alarm:

  • Check fuses in the unit.

  • Check with a multimeter that the device provides charging output, (230 V ) in mains operation and in battery operation.

  • Batteries have sufficient voltage, (27 V). Measure the battery terminals.

Control measures in case of alarm UPS - Overvoltage, too high charging current

If the charging voltage in normal operation exceeds 27.9 V, the charging is disconnected.

Check with a multimeter that the device's charge does not exceed 27.9 V.

Contact support for further assistance with adjusting the voltage of the power supply unit.

Test load in UPS (part of self-test system)

The unit is tested weekly against an internal test load. This is to check that the output voltage is sufficient for UPS operation and thus that the batteries are not aged.

Are alarms given when batteries are recharged after a power outage?

No alarms are given when the batteries are charged after a mains failure.

Technical facts alarm: Incorrect charging voltage

Alarm for incorrect charging voltage is given if the charger's voltage falls below 26.5 V.

Undervoltage may be natural after prolonged discharge, UPS operation. To ensure that the power supply does not break during recharging, a test is made every 45 minutes that the charging voltage is correct.

Alarms for incorrect charging voltage/broken power supply are displayed on the panel and via potential-free relay switching.

Technical facts alarm: Overvoltage

If the charging voltage in normal operation exceeds 27.9 V, the charging is disconnected. An alarm is also given on potential-free relay switching.

Technology facts alarm: Aged battery

Every week, batteries are tested with a high, predetermined and short-term load current across internal load resistors that correspond to the batteries' rated power. Current battery capacity is measured. The microprocessor takes a "fingerprint" of the current state of the battery in the load test. The value taken is then compared with the programmed battery value. In tests that give an indication of between 20% - 40% of the original battery capacity, an alarm for an aged battery is given. Alarm is also given on potential-free relay switching/Sum-alarm.

Technology facts alarm: Inverter test

Every week the unit is tested with internal load. If the unit's inverter does not provide sufficient output voltage, an alarm is given. Alarm is also given on potential-free relay switching.

SIN

SIN - UPS Product sheet / technical data

Figure 2. UPS SINUS 300W M
UPS SINUS 300W M


Technical specifications

These technical specifications are subject to change without notice.

SINUS UPS name, article number and e-number

Name

Article number

E-number

SINUS UPS 300W M

ME01U0021FP003

52 136 21

Maximum rated power

Maximum rated power

Continuous effect

SIN 300W M

300 W

ABOUT UPS

The UPS are designed with the latest switch technology and microprocessor monitoring, for maximum efficiency and reliability, providing long life for both electronics and batteries. UPS is well protected with protection against overtemperature, overload, short circuit.

Fixed installation

The product is intended for fixed installation. The battery backup must be installed by a qualified installer.

Areas of use

SINUS UPS is mostly used for camera surveillance, PoE switches and other security systems. Sinus UPS is also used for gates and gate control of smaller and larger industrial and garage doors.

  • Camera surveillance,

  • PoE switches and other security systems.

  • Gate and door control of smaller and larger industrial and garage doors.

Regulations and certifications

Requirements that the product meets

EMC:

EMC Directive 2014 / 30EU

Electricity:

Low voltage directive: 2014/35 / EU

EN 62368-1

CE:

CE directive according to: 765/2008

Emission:

EN61000-6-: 2001 EN55022: 1998: -A1: 2000, A2: 2003 Klass B, EN61000-3-2: 2001

Immunity:

EN61000-6-2:2005, EN61000-4-2, -3, 4, -5, -6, -11

LVD

EN60950

ce-marking-logo-kov.jpg
soptunna_atervinning.ai

Circuit boards - Technical data

Technical data: CEO 3

Info

Explanation

Article title

CEO3

Product description

CEO 3 is the next generation circuit board for simpler battery backups. Advanced functions that were not previously possible in simpler battery backups are now available as standard. CEO 3 is a reliable heart in simpler battery backups with fewer components than before, which reduces the environmental impact.

Measure

120 x 55 mm x 52 mm

Voltage form

1-phase sine

Fuses

See table: Fuses

Fuse on output

24 V

Outputs

Output: four load outputs 1-4 which are prioritized load outlets. (= always voltage).

Insurance

Load output: + secured.

Indication

Display showing operating status, alarms and faults. Operating indication: one indication diode per load output +/-. Solid green light = normal operation.

230 V voltage in

Voltage

Explanation / comment

Voltage in:

230V -15%, + 20% in mains operation.

Mains power:

charger max 0.4A + load.

230 V output voltage

Voltage OUT

Explanation / comment

Voltage out:

230 V - 10% in battery operation.

Voltage form:

Single-phase sine voltage.

Efficiency, approx:

90%

Idle power, approx:

10 W

Battery charge

I / O according to DIN 41773 Current limitation.

Protection

Type of protection

Explanation

Current limitation, electronic:

Type 300% of rated capacity.

Short-circuit protection:

Shutdown within 5 sec in case of heavy overload / short circuit according to UPS EN62040-1-1 standard.

Automatic restart when mains voltage returns.

Depth discharge protection:

When the battery terminal voltage is less than 19 V.

Overcharge protection:

Disconnection of charging voltage during overcharging.

Automatic fuse:

Batteries are secured.

Optional: Ground fault circuit breaker:

Can be installed on output (extra protection option according to EN62040-1-1).

Fuses Minisinus v8

On circuit boards

Fuse

Explanation

F1

T16A

Battery fuse

Self-test

Type of self-test

Explanation

Battery charge

Continuous monitoring of battery chargers.

Battery aging

Automatic test loading of batteries under high, short-term discharge current to detect battery aging. The test compares measured battery capacity with programmed values to give an alarm when the battery has lost 20% - 40% capacity of new value and should be replaced.

Inverters

Test load of UPS (corresponding rated power over internal test load) to check function and sufficient output voltage.

Alarm

All alarms occur on potential-free relay switching.

Alarm type

Explanation

Power outage alarm

Alarm in case of network interruption adjustable time delay from direct to 10 h (3s, 3, 15, 30m, 1, 2, 4, 10h).

Sum Alarm, Self-Test:

Incorrect charging voltage (over- or under-voltage), aged battery that should be replaced or a malfunctioning inverter.

Technical data enclosures

Enclosures - Technical Data M

Info

Explanation

Name

M

Enclosure class

IP 20

Measure

Height: 242 mm, width: 350 mm, depth: 150 mm.

Height units

-

Mounting

Wall

Ambient temperature

+ 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.

Environment

Environmental class 1, indoors. 20% ~ 90% relative humidity

Material

Powder coated sheet

Color

White

Cable entries, number

5

Batteries that fit

2 pcs 12 V 7.2 Ah or

2 pcs 12 V 14 Ah.

Batteries - recommended, not included

Batteries are not included they are sold separately

Batteries are sold separately.

14 Ah, 12 V AGM battery

Fits in

Number of batteries

SINUS UPS 300W M

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

14 Ah

Table 6. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V14-01

5230537

UPLUS 12V 14Ah 10+ Design Life battery

Flat pin 6.3 mm

151x98x101 mm

4.2 kg

UPLUS



Link to the latest information

Products and software are subject to updates, you will always find the latest information on our website.

Sinus UPS

Warranty, support, country of manufacture and country of origin

Warranty

The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product's lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik's discretion) occour after the warranty period has expired.

Support

Do you need help with installation or connections? Our support phone is available: Monday-Thursday 08: 00-16: 00 and Fridays 08: 00-15: 00. Telephone support is closed between 11: 30-13: 15.

You will find answers to many questions at: www.milleteknik.se/support

Phone: +46 31-340 02 30

Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.

Spare parts

Contacted support for questions about spare parts.

Support after the warranty period

Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are added after the warranty period has expired.

Questions about product performance?

Contact sales: 46 31-340 02 30, e-mail: sales@milleteknik.se

Contact us

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31-34 00 230

www.milleteknik.se

Country of manufacture

Country of manufacture / country of origin is Sweden. For more information, contact your seller.

Designed and produced by: Milleteknik AB

Designed and produced by Milleteknik AB

Address and contact details

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

+46 31 340 02 30

www.milleteknik.com