About NEO

NEO is normally used in security systems where the requirements are higher for more functions, alarm functions, longer backup operating times or when the battery backup is to handle higher loads.

About translation of this document

User manual and other documents are in the original language in Swedish. Other languages are machine translated and not reviewed, errors may occur.

Read this first!

If possible, leave 100 mm of free space.

The system is intended for use in a controlled indoor environment.

Only authorized persons should install and maintain the system.

It is the installer's responsibility to ensure that the system is suitable for its intended use.

Documents accompanying the system must be kept in or in its immediate vicinity.

Ventilation should not be covered. Mains voltage should be disconnected during installation.

All information subject to change.

Upon installation of this product, the installer acknowledges and accepts the limitations of this product as described in this manual.

Instructions original language: Swedish.

Component overviews

Component overview NEO FLX L

RCO_FLX_L_komponetoeversikt_utan_batteribox.pdf
Table 1. Component overview

Letter

Explanation

A

Console, reversible for mounting in a wall or 19" rack.

B

Optional: Tamper switch

C

Cabinet in powder-coated sheet metal.

D

Space for optional cards

E

Power supply, located on the back in some configurations.

F

Cable entries.

G

Motherboard.

H

Lockable door.

I

Space for batteries.



Enclosures

Bracket

The supplied brackets can be attached in two ways: When mounting on a wall, the brackets must sit backwards, against the wall. When mounting in a 19" rack, the bracket must sit at the front of the unit.

Konsol_pa_FLX_L.png

No

Explanation

A

Console is pushed in from the bottom up. Slide the top bracket in first.

B

Clip clicks in when bracket is pushed in correctly.

Mounting

Use the appropriate screw for mounting on a wall or in a 19" rack. Screws for mounting on a wall or in a rack are not included.

Batteries - placement and connection

Connection of batteries in FLX S, FLX M and FLX L

Battery wiring is mounted on the circuit board upon delivery. Pictures below only show how to connect wiring.

  1. Place the batteries in the cabinet with the battery terminals facing outwards.

  2. Connect the battery cable. Red cable on + and black cable on -.

  • If possible, disconnect mains voltage when replacing the battery.

Figure 1. Wiring diagram for batteries in battery backup
Wiring diagram for batteries in battery backup

Connect the terminals correctly so that you do not damage the equipment.



Note when connecting batteries

When connecting batteries to NEO, cables with flat pins must not be used. In the picture marked with "NOVA ONLY"

NEO_KABLAGE.png

Motherboard description

Connect in this order

To minimize the risk of errors that may occur in connection with a short circuit, connections to the motherboard must be made in this order.

CEO3_uP.png
Table 2. Connect in this order

Nr

Explanation

1

Connect alarm.

2

Connect load.

3

Connect batteries

4

Connect mains.



Figure 2. Description: CEO3 uP
Description: CEO3 uP


On PCB

Explanation

D6

Indicator diode.

JU2

Jumper for alarm control. When the jumper is mounted, the alarm limit is lowered.

P1:1-3

Mains connection.

P2:1-2

Load output, + / -.

P2:3-4

Load output, + / -.

P3:1-3

Alarm output, NC, CO, NO.

P3:4-6

Alarm output, NC, CO, NO.

Connect alarm on P3

Alarm is connected to terminal P3

Table 3. Connect alarm P3

P3:1-6

Explanation

Sum alarm

P3:1

NC

P3:2

Com

P3:3

NO

Sum-alarm*

P3:4

NC

P3:5

Com

P3:6

NO



Total alarm: Broken fuse on load, broken fuse from external distribution board, broken battery fuse, low battery voltage in battery operation, batteries not connected, overvoltage.

Connect load

Anslut_last_2_utgangar.png
Table 4. Load connections

Circuit board number

Explanation

P2: 1

Connection for load 1 +

P2: 2

Connection for load 1 -

P2: 3

Connection for load 2 +.

P2: 4

Connection for load 2 -.



Max current

The maximum current must not be exceeded. Max current is indicated on nameplate on the device.

Danger

Mains voltage must be disconnected when working with stripped cables. It is the installer's responsibility to ensure that the correct skills are available for connecting 230 V to the unit. Maximum cable area is 4 mm2

Connect mains

Pull wiring through the cable entry on the cabinet.

If possible, secure the mains cable with cable ties where possible.

Electrical network cabling shall be kept separate from other cabling to avoid EMC interference.

Figure 3. Connect the mains to the motherboard
Connect the mains to the motherboard

Connect the mains cable to the terminal before it is put back on the motherboard. Secure F and N with cable ties for electrical safety.



Table 5. Electrical network connections

Letter

Explanation

F

Phase

N

Neutral

PE

Protective earth



Electrical mains connection 230 V AC on circuit board

Check that the marking on the circuit board matches the cable arrangement on the terminal block.

Control alarm limit

Alarm for low battery voltage in battery operation can be controlled.

By jumpering JU2, the limit for when the unit should give an alarm can be lowered.

Alarms are given when the battery voltage in battery drops below the limit.

Fuses

Unit

Fuse

Type

Explanation

All units

F1

T2,5A

Mains fuse

F2, F6

T5A

Load fuse +

F2, F6

T10A

Load fuse +

All units

F7

T16A

Battery fuse

Fuse Replacement Warning (A)

There is a risk of damage if the fuse is changed to a larger one than what the unit is delivered with. The function of the fuse is to protect the connected load and cables against damage and fire. It is not possible to change the fuse to a larger one to increase the power output.

Commissioning - how to start the unit

The unit works normally when the indicator LED on the outside of the cabinet door lights up with a solid green light. See front panel for other status indications.

It may take up to 72 hours before the batteries are fully charged.

Alarm displayed on cabinet door

In normal mode, the indicator LED shows a solid green light.

222-114.png

The indicator diode (LED) shows

Explanation

Solid green light

Normal operation.

Slow green flashes

Not available for NEO.

Fast green flashes

Not available for NEO.

Solid yellow light

Mains failure.

Slow yellow flashes

Not available for NEO.

Rapid yellow flashes

Not available for NEO.

Solid red light

Fuse error / charger fault / batteries not connected.

Slow red flashes

Not available for NEO.

Rapid red flashes

Not available for NEO.

No light / off

Deep discharge protection is activated. (System shutdown).

When operating system: If the indicator LED is off, deep discharge protection has come into force.

NEO Product Sheet

NEO Battery backup with more alarm functions

Figure 4. NEO FLX L
NEO FLX L

NEO FLX L is mounted on a wall or in a 19" rack.



Technical specifications

These technical specifications are subject to change without notice.

NEO - Name, article number and e-number

Name

Article number

E-number (SV)

NEO 24V 5A FLX L

FL01N10224P050

52 136 96

NEO 24V 10A FLX L

FL01N10224P100

52 136 97

NEO battery backup for security installations

NEO is normally used in facilities where the requirements are higher regarding greater flexibility, more alarm functions, longer backup operating times or when the battery backup needs to handle higher loads. The NEO series offers controlled charging (intelligent charging), which means that when the batteries are fully charged, they will be electronically disconnected for standby mode for up to 20 days or when the batteries have reached 26.7 V (24 V). By discharging the batteries and recharging them continuously (instead of never using them), the system extends the life of the battery by up to 50%. The batteries automatically connect in less than 50 microseconds when needed.

Flexibility

NEO FLX S can have an extra battery box. NEO FLX M and NEO FLX L with 1-4 extra battery boxes. NEO FLX M and NEO FLX L with battery shelves in 19 ”rack *. * The battery boxes and shelves are connected via a 9-pin connector. The battery box has room for up to 2 pcs. 45 Ah batteries per battery box. Battery shelves have room for 2 pcs. 45 Ah batteries (Medium) and up to 2 pcs. 150 Ah batteries (Large) per each battery shelf.

Area of use

NEO supplies power to access systems, alarm systems or other security products in a building that are powered by 24 V DC. The rectifier in the power supply converts 230 V DC down to 24 V DC. Batteries, for example the access system, continue when the power grid goes down. Long life, energy efficient and support is available if something goes wrong, now or in 10 years.

Fixed installation

The product is intended for fixed installation. The battery backup must be installed by a qualified installer.

Regulations and certifications

Requirements that the product meets

EMC:

EMC Directive 2014 / 30EU

Electricity:

Low voltage directive: 2014/35 / EU

CE:

CE directive according to: 765/2008

ce-marking-logo-kov.jpg
soptunna_atervinning.ai

Expected operating time in the event of a power failure ( with new batteries)

System voltage

Number of batteries

Battery type

Unit +

battery box *

Load:

2 A

Load:

4 A

Load:

8 A

Load:

10 A

Load:

14 A

Load:

18 A

24 V

2 pcs.

45 Ah

1+0

21 h

12 h

4 h

3 h

2 h

1.5 h

24 V

4 pcs

45 Ah (90 Ah)

1+1

42 h

20 h

12 h

8 h

5 h

2.5 h

24 V

6 pcs

45 Ah (135 Ah)

1+2

64 h

30 h

15 h

12 h

9 h

6 h

24 V

8 pcs

45 Ah (180 Ah)

1+3

82 h

42 h

20 h

16 h

12 h

10 h

24 V

10 pcs

45 Ah (225 Ah)

1+4

108 h

54 h

26 h

20 h

15 h

13 h

* Example: 1 + 2 means that there is 1 battery backup with 2 battery boxes connected. 1 + 0 means that it is a battery backup without a battery box.

Circuit boards - Technical data

Technical data: CEO 3

Table 7. CEO3-ECO

Info

Explanation

Article name

CEO3-ECO

Product description

CEO 3 is the next generation circuit board for simpler battery backups. Advanced functions that were not previously possible in simpler battery backups are now available as standard. CEO 3 is manufactured with fewer components than before, which reduces the environmental impact.

Measure

120 x 55 mm x 52 mm

Own consumption

50 mA

Fuses

See table: Fuses.

Outputs

Output: two load outputs.

Insurance

Load output: + secured.

Max load

Maximum load is 10 A per load output (T2A is mounted from the factory) and the card's total load must not exceed 16 A.

Alarm outputs

Alarm outputs: Sum alarm in case of fuse fault, see indication below. Alarm on potential-free relay contact.

Alarm

Sum alarm, Mains failure, fuse failure, charger failure, batteries not connected.

Alarm via

Triggered load securing, potential-free shifting, CO / NO.

Indication

Display showing operating status, alarms and faults. Operating indication: one indication diode per load output +/-. Solid green light = normal operation.



Control alarm limit with JU2
Control alarm limit

Alarm for low battery voltage in battery operation can be controlled.

By jumpering JU2, the limit for when the unit should give an alarm can be lowered.

Alarms are given when the battery voltage in battery drops below the limit.

Fuses

Unit

Fuse

Type

Explanation

All units

F1

T2,5A

Mains fuse

F2, F6

T5A

Load fuse +

F2, F6

T10A

Load fuse +

All units

F7

T16A

Battery fuse

Fuse Replacement Warning (A)

There is a risk of damage if the fuse is changed to a larger one than what the unit is delivered with. The function of the fuse is to protect the connected load and cables against damage and fire. It is not possible to change the fuse to a larger one to increase the power output.

Power supply

Nätagg - Tekniska Data LRS-150-12

Power supply - Technical Data LRS-150-24

In:

NEO 24V 5A FLX L

Info

Explanation

Output voltage

27.3 V

Output current:

0 A - 6.5 A

Output voltage, ripple

200 mVp-p

Overvoltage

28.8 V - 33.6 V

Voltage recharge, ripple / current limitation

Less than 0.6 Vp-p

Efficiency

89%

Current limitation

110% - 140%

Constant voltage

+/- 0.5%

Regulatory accuracy

+ / - 1.0%

Input current (230 V)

1,7 A

Mains voltage frequency

47 Hz- 63 Hz

Mains voltage

230 V AC - 240 V AC

Brand effect

156 W

Temperature range

-30°C - +70°C

Humidity range

20% - 90% RH non-condensed

Power supply - Technical Data RSP-320-24

In:

NEO 24V 10A FLX L

Info

Explanation

Output voltage

27.3 V

Output current

0 A - 13.4 A

Output voltage, ripple

150 mVp-p

Overvoltage

27.6 V - 32.4 V

Voltage recharge, ripple / current limitation

Less than 1.2 Vp-p

Efficiency

89%

Current limitation

105% - 135%

Constant voltage

+/- 0.5%

Regulatory accuracy

+/- 1.0%

Input current (230 V)

2 A

Mains voltage frequency

47 Hz- 63 Hz

Mains voltage

230 V AC - 240 V AC

Brand effect

321.6 W

Temperature range

-30°C - +70°C

Humidity range

20% - 90% RH non-condensed

Technical data enclosures

Enclosures - Technical Data FLX L

Info

Explanation

Name

FLX L

Enclosure class

IP 32

Measure

Height: 444 mm, width 438 mm, depth 212 mm

Height units

10 HE

Mounting

Wall or 19 "rack

Ambient temperature

+ 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.

Environment

Environmental class 1, indoors. 20% ~ 90% relative humidity

Material

Powder coated sheet

Color

Black

Cable entries, number

4

Batteries that fit

2 st 12 V 45 Ah

Place for fan

Yes

Link to the latest information

Products and software are subject to updates, you will always find the latest information on our website.

NEO

Warranty, support, country of manufacture and country of origin

Warranty

The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product's lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik's discretion) occour after the warranty period has expired.

Support

Do you need help with installation or connections? Our support phone is available: Monday-Thursday 08: 00-16: 00 and Fridays 08: 00-15: 00. Telephone support is closed between 11: 30-13: 15.

You will find answers to many questions at: www.milleteknik.se/support

Phone: +46 31-340 02 30

Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.

Spare parts

Contacted support for questions about spare parts.

Support after the warranty period

Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are added after the warranty period has expired.

Questions about product performance?

Contact sales: 46 31-340 02 30, e-mail: sales@milleteknik.se

Contact us

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31-34 00 230

www.milleteknik.se

Country of manufacture

Country of manufacture / country of origin is Sweden. For more information, contact your seller.

Designed and produced by: Milleteknik AB

Designed and produced by Milleteknik AB

Batteries - recommended, not included

Batteries are not included they are sold separately

Batteries are sold separately.

45 Ah, 12 V AGM battery

Fits in

Number of batteries

NE0 24V 5A FLX L

2

NE0 24V 10A FLX L

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

45 Ah

Table 9. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V45-01

5230546

UPLUS 12V 45Ah 10+ Design Life battery

M5 Bult

197x165x170 mm

14.5 kg

UPLUS



Address and contact details

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31 340 02 30

info@milleteknik.se

www.milleteknik.com