PRO3 -Dip switch S3

Address setting for external communication (Dip switch 1-4)

Dip-Switch S1: 1-4 sets addressing.

Table 1. Addressing Dip-Switch 1-4

Dip: 1

Dip: 2

Dip: 3

Dip:4

Adress 1

ON

OFF

OFF

OFF

Adress 2

OFF

ON

OFF

OFF

Adress 3

ON

ON

OFF

OFF

Adress 4

OFF

OFF

ON

OFF

Adress 5

ON

OFF

ON

OFF

Adress 6

OFF

ON

ON

OFF

Adress 7

ON

ON

ON

OFF

Adress 8

OFF

OFF

OFF

ON

Adress 9

ON

OFF

OFF

ON

Adress 10

OFF

ON

OFF

ON

Adress 11

ON

ON

OFF

ON

Adress 12

OFF

OFF

ON

ON

Adress 13

ON

OFF

ON

ON

Adress 14

OFF

ON

ON

ON

Adress 15

ON

ON

ON

ON



Mains failure delay (dip 5-6)

It is possible to change the time for when the alarm for a power outage should be given. Use the matrix to set the alarm.

Table 2. Mains failure delay

Alarms for mains failure are given after:

Dip 5

Dip 6

3 seconds

OFF

OFF

30 minutes

ON

OFF

60 minutes

OFF

ON

240 minutes (4 hours)

ON

ON



Low battery voltage (dip 7)

Dip: 7 has the same function regardless of whether the unit is in mains or battery operation or whether the tamper switch is held down.

Table 3. Low battery voltage

Alarm for low battery voltage is given when

Dip 7

22,8 V*

ON

24 V

OFF

*25% of battery capacity remains.



Battery test (dip 8)

To do a battery test, dip 8 needs to change position and five seconds need to pass before the test is initiated.

  • If dip 8 in original position is on OFF then switch dip 8 to: ON (wait 5 seconds) and then switch back to OFF.

  • If dip 8 in original position is on ON then switch dip 8 to: OFF (wait 5 seconds) and then switch back to ON.

This activates the battery test after 3-8 seconds. The battery test lasts for about 6 seconds and then the LED flashes yellow quickly. Aged battery alarms may be indicated while the battery test is being performed.

Only reset dip 8 when the test is complete.

Reboot to confirm changes in address, battery and alarm settings to parent system

After the dip-switch has been set for various parameters, the device's software needs to be restarted. This is for the new settings to be stored and take effect.

Important

Rebooting according to this procedure does not   interrupt the output voltage.

Restarting the device software is done by jumpering J11 (PRO3)

Important

Reboot must be done every time a change is made to the device.

NEO cannot be connected to communication/UC.

Reset after battery replacement -PRO3

After battery replacement, the device needs to measure the capacity of new batteries and clear previously set battery capacity. All alarms are cleared from the units memory, statistics remains and can not be cleared.

  • Insert jumper on J11 and remove jumper on J11

After doing step, the battery capacity is cleared in the units memory and is ready to read the new battery capacity.

This procedure needs to be done each time the batteries are replaced or when connecting a battery box.