About

Name

Item number

Email number

Power Supply 24V 15A 1U

1U01D10024P1501

5213517

Power supply 24V 15A is a rack-mounted power supply that can be used independently or together with Redundancy panel 1U or with a battery backup from Milleteknik.

Area of use: To supply power to access systems, locking systems and fire alarms and other facilities operated with 24 V DC.

Read this first!

If possible, leave 100 mm of free space.

The system is intended for use in a controlled indoor environment.

Only authorized persons should install and maintain the system.

It is the installer's responsibility to ensure that the system is suitable for its intended use.

Documents accompanying the system must be kept in or in its immediate vicinity.

Ventilation should not be covered. Mains voltage should be disconnected during installation.

All information subject to change.

Upon installation of this product, the installer acknowledges and accepts the limitations of this product as described in this manual.

Instructions original language: Swedish.

Component overview

Figure 1. Front
Front


No

Explanation

1

Load on/off

2

LED

Figure 2. Back
Back


No

Explanation

1

Mains, 230 V in

2

Double sum alarm, NO/COM/NC+NO/COM/NC.Sum alarm: alarm in the event of a loss of voltage from the power supply unit after the load fuse has tripped.

3

Load -- / ++

Enclosures

Installation in 19" rack

The unit must be mounted in a 19" rack. Bracket is screwed into rack with M6 screw and basket nut, at least one on each side. Use the appropriate screw and nut for the rack. Screw and nut not included.

Montera1U.png

No .

Explanation

1

The unit is screwed into a 19" rack.

Mounting

Mains connection

Use 3-pin mains plug for connection to 230 V.

Connect load

24 V load is connected via quick contact. (Redundancy panel 1U is also connected here.)

Component overviewComponent overview

Connect alarm

Alarm is connected on the back. NO/CO/NC. Use any connection, the alarms are duplicated.

Total alarm: Alarm in the event of loss of voltage from the power supply unit after load protection.

Alarm functions

Double total alarm: Alarm in the event of loss of voltage from the power supply after load protection.

Commissioning

After connection, startup must take place in the following steps:

  1. Connect load.

  2. Check that the fuse on the front is ON.

  3. Voltage setting of power grid.

The device works normally when the indicator diode on lights up with a solid green light.

Recovery

Reset the unit by completely de-energizing the unit.

Disconnect battery wiring and mains voltage and reconnect after 5 seconds.

Panel explanation

Table 1. Indicator diode on the front

LEDs

Explanation

Solid green

Ok - normal mode

Flashing green

Alarm

Turned off

No power from mains / not connected to mains / Fuse has tripped.



Regulations and certifications

Requirements that the product meets

EMC:

EMC Directive 2014 / 30EU

Electricity:

Low voltage directive: 2014/35 / EU

CE:

CE directive according to: 765/2008

ce-marking-logo-kov.jpg
soptunna_atervinning.ai

Technical data enclosures

Technical data 1U

Info

Explanation

Name

1U

Enclosure class

IP 20

Measure

Height: 44 mm, width: 244 mm, depth: 280 mm.

Height units

1

Mounting

19 "rack

Ambient temperature

+ 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.

Environment

Environmental class 1, indoors. 20% ~ 90% relative humidity

Material

Powder coated sheet metal

Color

Black

Cable glands, number

8

Power supply

Power supply - Technical Data HRP-300-24

In:

Power Supply 24V 15A 1U

Info

Explanation

Output voltage

27.3 V

Output current

0 A - 14 A

Output voltage, ripple

150 mVp-p

Overvoltage

30 V - 34.8 V

Voltage recharge, ripple / current limitation

Less than 1.2 Vp-p

Efficiency

87%

Current limitation

105% - 135%

Constant voltage

+/- 0.5%

Regulatory accuracy

+/- 1.0%

Input current (230 V)

1,8 A

Mains voltage frequency

47 Hz- 63 Hz

Mains voltage

230 V AC - 240 V AC

Brand effect

336 W

Temperature range

-40 ° C - + 70 ° C

Humidity range

20% - 90% RH non-condensed

Warranty, support, country of manufacture and country of origin

Warranty

The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product's lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik's discretion) occour after the warranty period has expired.

Country of manufacture

Country of manufacture / country of origin is Sweden. For more information, contact your seller.

Designed and produced by: Milleteknik AB

Designed and produced by Milleteknik AB

Product life cycle, environmental impact and recycling

The product is designed and constructed for a long service life, which reduces the environmental impact. The product's service life depends on, among other things, environmental factors, mainly ambient temperature, unforeseen load on components such as lightning strikes, external damage, handling errors, and more. Products are recycled by being handed over to the nearest recycling station or sent back to the manufacturer. Contact your distributor for more information. Costs that arise in connection with recycling are not reimbursed.

soptunna_atervinning.ai

About this document

Article number of the document:

This document is subject to change without prior notice.

All information is published with reservation for printing errors.

About translation of this document

User manual and other documents are in the original language in Swedish. Other languages are machine translated and not reviewed, errors may occur.

Address and contact details

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31 340 02 30

info@milleteknik.se