About
Name | Item number | Email number |
---|---|---|
Power Supply 24V 15A 1U | 1U01D10024P1501 | 5213517 |
Power supply 24V 15A is a rack-mounted power supply that can be used independently or together with Redundancy panel 1U or with a battery backup from Milleteknik.
Area of use: To supply power to access systems, locking systems and fire alarms and other facilities operated with 24 V DC.
Read this first!
If possible, leave 100 mm of free space.
The system is intended for use in a controlled indoor environment.
Only authorized persons should install and maintain the system.
It is the installer's responsibility to ensure that the system is suitable for its intended use.
Documents accompanying the system must be kept in or in its immediate vicinity.
Ventilation should not be covered. Mains voltage should be disconnected during installation.
All information subject to change.
Upon installation of this product, the installer acknowledges and accepts the limitations of this product as described in this manual.
Instructions original language: Swedish.
Component overview
No | Explanation |
---|---|
1 | Load on/off |
2 | LED |
No | Explanation |
---|---|
1 | Mains, 230 V in |
2 | Double sum alarm, NO/COM/NC+NO/COM/NC.Sum alarm: alarm in the event of a loss of voltage from the power supply unit after the load fuse has tripped. |
3 | Load -- / ++ |
Enclosures
Installation in 19" rack
The unit must be mounted in a 19" rack. Bracket is screwed into rack with M6 screw and basket nut, at least one on each side. Use the appropriate screw and nut for the rack. Screw and nut not included.
No . | Explanation |
---|---|
1 | The unit is screwed into a 19" rack. |
Mounting
Mains connection
Connect load
24 V load is connected via quick contact. (Redundancy panel 1U is also connected here.)
Connect alarm
Alarm is connected on the back. NO/CO/NC. Use any connection, the alarms are duplicated.
Total alarm: Alarm in the event of loss of voltage from the power supply unit after load protection.
Alarm functions
Double total alarm: Alarm in the event of loss of voltage from the power supply after load protection.
Commissioning
After connection, startup must take place in the following steps:
Connect load.
Check that the fuse on the front is ON.
Voltage setting of power grid.
The device works normally when the indicator diode on lights up with a solid green light.
Recovery
Reset the unit by completely de-energizing the unit.
Disconnect battery wiring and mains voltage and reconnect after 5 seconds.
Panel explanation
LEDs | Explanation |
---|---|
Solid green | Ok - normal mode |
Flashing green | Alarm |
Turned off | No power from mains / not connected to mains / Fuse has tripped. |
Regulations and certifications
Requirements that the product meets
EMC: | EMC Directive 2014 / 30EU |
Electricity: | Low voltage directive: 2014/35 / EU |
CE: | CE directive according to: 765/2008 |
Technical data enclosures
Technical data 1U
Info | Explanation |
---|---|
Name | 1U |
Enclosure class | IP 20 |
Measure | Height: 44 mm, width: 244 mm, depth: 280 mm. |
Height units | 1 |
Mounting | 19 "rack |
Ambient temperature | + 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C. |
Environment | Environmental class 1, indoors. 20% ~ 90% relative humidity |
Material | Powder coated sheet metal |
Color | Black |
Cable glands, number | 8 |
Power supply
Power supply - Technical Data HRP-300-24
In: |
---|
Power Supply 24V 15A 1U |
Info | Explanation |
---|---|
Output voltage | 27.3 V |
Output current | 0 A - 14 A |
Output voltage, ripple | 150 mVp-p |
Overvoltage | 30 V - 34.8 V |
Voltage recharge, ripple / current limitation | Less than 1.2 Vp-p |
Efficiency | 87% |
Current limitation | 105% - 135% |
Constant voltage | +/- 0.5% |
Regulatory accuracy | +/- 1.0% |
Input current (230 V) | 1,8 A |
Mains voltage frequency | 47 Hz- 63 Hz |
Mains voltage | 230 V AC - 240 V AC |
Brand effect | 336 W |
Temperature range | -40 ° C - + 70 ° C |
Humidity range | 20% - 90% RH non-condensed |
Warranty, support, country of manufacture and country of origin
Warranty
The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product's lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik's discretion) occour after the warranty period has expired.
Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.
Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB
Product life cycle, environmental impact and recycling
The product is designed and constructed for a long service life, which reduces the environmental impact. The product's service life depends on, among other things, environmental factors, mainly ambient temperature, unforeseen load on components such as lightning strikes, external damage, handling errors, and more. Products are recycled by being handed over to the nearest recycling station or sent back to the manufacturer. Contact your distributor for more information. Costs that arise in connection with recycling are not reimbursed.
About this document
Article number of the document:
This document is subject to change without prior notice.
All information is published with reservation for printing errors.
About translation of this document
User manual and other documents are in the original language in Swedish. Other languages are machine translated and not reviewed, errors may occur.
Address and contact details
Milleteknik AB |
Ögärdesvägen 8 B |
S-433 30 Partille |
Sweden |
+46 31 340 02 30 |
info@milleteknik.se |
www.milleteknik.com |